Precise time synchronization is critical for IEC 61850 digital substations, power grids, and industrial automation systems. Although IEEE 1588 Precision Time Protocol (PTP) achieves sub-microsecond accuracy, it was not designed with built-in security mechanisms, leaving it exposed to a growing and diverse threat landscape. This paper presents a systematic review of attack and defense techniques targeting IEEE 1588 PTP. We develop a structured taxonomy of six attack categories with experimentally validated deviation ranges where available and characterized attack bounds otherwise, map eleven defense mechanisms against this taxonomy, and identify four key analytical findings. Our analysis reveals that no single defense mechanism provides comprehensive protection, that kernel-level attacks represent the most critical unaddressed gap, and that quantitative Wide Area Monitoring, Protection and Control (WAMPAC) impact thresholds derived from hardware-in-the-loop experiments should anchor the design of future PTP security solutions.